Instrumentation and control
4–20 mA and 0–10 V signals
Conversion between standard analog signals and process values.
Instrumentation and control
4–20 mA current from percent
I = 4 + 16p/100→Instrumentation and controlPercent from 4–20 mA
p = (I − 4)/16 × 100%→Instrumentation and controlProcess value from 4–20 mA
PV = LRV + (I−4)(URV−LRV)/16→Instrumentation and control4–20 mA from process value
I = 4 + 16(PV−LRV)/(URV−LRV)→Instrumentation and control0–10 V voltage from percent
U = 10p/100→Instrumentation and controlProcess value from 0–10 V
PV = LRV + U(URV−LRV)/10→Instrumentation and controlUniversal scale-to-signal conversion
S = Smin + (X−Xmin)/(Xmax−Xmin)(Smax−Smin)→